Back | Next |
Ministry of Environment and Forests
Notification
New Delhi, the 17th May, 2002
G.S.R. 371(E):Â In exercise of the powers conferred by
sections 6 and 25 of the Environment (Protection) Act, 1986 (29 of 1986), the
Central Government hereby makes the following rules further to amend the
Environment (Protection) Rules, 1986, namely:- 1. 2. In the Environment (Protection) Rules, 1986 (herein after
referred to as the said rules), in Schedule I, ?
"94. NOISE LIMIT FOR GENERATOR SETS RUN WITH DIESEL
1. Noise limit for diesel generator sets (upto 1000 KVA)
manufactured on or after the 1st July, 2003.
2. Noise limit for DG sets not covered by paragraph 1. 3. LIMITS OF NOISE FOR DG SETS (UPTO 1000 KVA) MANUFACTURED
ON OR AFTER THE 1ST JULY, 2003
Every manufacturer or importer (herein after referred to
as "supplier") of DG set (herein after referred to as
"product") to which these regulations apply must have valid
certificates of Type Approval and also valid certificates of Conformity of
Production for each year, for all the product models being manufactured or
imported from 1SUP>st July, 2003 with the noise limit specified in
paragraph 1. No person shall sell, import or use of a product model,
which is not having a valid Type Approval certificate and Conformity of
Production certificate. The following agencies are authorized to carry out such
tests as they deem necessary for giving certificates for Type Approval and
Conformity of Production testings of DG sets and to give such certificates:-
The compliance and testing procedure shall be prepared
and published by the Central Pollution Control Board, with the help of the
certification agencies. 95. EMISSION LIMITS FOR NEW DIESEL ENGINES (UP TO 800 KW) FOR
GENERATOR SETS (GENSETS) APPLICATIONS
The emission limits for new diesel engines up to 900 kw,
for gensets applications shall be as given in the Table below:
Table
These rules shall apply to all new diesel engines for
genset applications (herein after referred to as 'engine') manufactured in
India and all diesel engines for genset applications and diesel gensets
(herein after referred to as 'product'), imported into India, after the
effective date:
Provided that these rules shall not apply to:
Every manufacturer of engine or every importer of
engine or product must have valid certificates of Type. Approval and
certificates of Conformity of Production for each year, for all engine
models being manufactured or for all engine or product models being
imported, after the effective date with the emission limit as specified in
paragraph 1. No person shall sell, import or use of an engine or a
product which is not having a valid Type Approval certificate and
Conformity of Production certificate as per paragraph 3. All engines up to 20 kw (individually or as part of the
product) shall carry ISI mark and meet relevant BIS specifications (IS
1000 1). The following agencies are authorized to carry out such
tests as they deem necessary for giving certificates of Type, Approval and
Conformity of Production tests for Diesel engines and to give such
certificates:-
The compliance and testing procedure shall be prepared
and published by the Central Pollution Control Board with the help of the
Certification Agencies. The specification of commercial fuel applicable for
-diesel gensets shall be the same as applicable for commercial HSD(High
Speed Diesel) applicable for diesel vehicles in the area, from time to
time." 3. In the said rules, in Schedule VI, in Part E relating to
NOISE STANDARDS, in clause B, the entry "(d) Diesel generator for
domestic purposes" shall be omitted.
[F. No. Q-15022/2/2001-CPA]
C. VISWANATH, Jt. Secy.
Note:Â The principal rules were published in the
Gazette of India vide number S.O.844(E) 19th November, 1986 and subsequently
amended vide S.O.433(E) dated 18th April, 1987, S.O.64(E) dated 18th January,
1988, S.O.3(E) dated 3rd January, 1989, S.O.190(E) dated 15th March, 1989,
G.S.R. 913(E) the 24th October, 1989, S.O.12(E) dated the 8th January, 1990,
G.S.R.742(E) dated the 30thAugust, 1990, S.O.23(E) dated the 16th January,
1991, G.S.R. 93(E) dated the 21st February, 1991, G.S.R. 95(E) dated the 12th
February, 1992, G.S.R. 329(E) dated the 13th March, 1992, G.S.R. 475(E), dated
the 5th May, 1992, G.S.R. 797(E) dated the 1st October, 1992, G.S.R. 386(E)
dated the 28th April, 1993, G.S.R., 422,(E) dated the 19th May, 1993, G.S.R.
801(E) dated the 31st December, 1993, G.S.R. 176(E) dated the 3rd April, 1996,
G.S.R. 631(E) dated the 31st October, 1997, G.S.R. 504(E) dated the 20th
August, 1998, G.S.R. 7(E) dated the 2nd January, 1999, G.S.R. 682(E) dated the
5th October, 1999, G.S.R - 742(E) dated the, 25th September, 2000, G.S.R.
72(E) dated 6th February, 2001 and G.S.R.54(E) dated 22.1.2002.
The maximum permissible sound pressure level for new diesel generator (DG) sets
with rated capacity up to 1000 KVA, manufactured on or after the 1st
July, 2003 shall be 75 dB(A) at 1 metre from the enclosure surface.
The diesel generator sets should be provided with integral acoustic enclosure at
the manufacturing stage itself.
The implementation of noise limit for these diesel generator sets shall be
regulated as given in paragraph 3 below.
Noise limits for diesel generator sets not covered by paragraph 1, shall be as
follows:
Capacity
of diesel engines
Date
of implementation
Emission
Limits (g/kw-hr) for
Smoke
Limit (light absorption coefficient, m-1)(at full load)
Test
cycle
NOx
HC
CO
PM
Torque
%
Weighting
factors
Upto
19 kw
1.7.2003
9.2
1.3
5.0
0.6
0.7
100
0.05
1.7.2004
9.2
1.3
3.5
0.3
0.7
75
0.25
>19
kw upto 50 kw
1.7.2003
9.2
1.3
5.0
0.5
0.7
50
0.30
1.7.2004
9.2
1.3
3.5
0.3
0.7
25
0.30
>50
kw upto 260 kw
1.7.2003
9.2
1.3
3.5
0.3
0.7
10
0.10
>
260 kw upto 800 kw
1.7.2004
9.2
1.3
3.5
0.3.
0.7